|
WATER SUPPLY FACTOR W |
|
|
|
|
|
|
|
|
|
|
|
Water is the most common
extinguishing means. Factor W defines the minimum standard (including town
mains) required for the water supply and considers the type of water storage,
the hydrant network, the available flow and pressure. |
|
|
|
|
Water storage type |
|
|
1. Water storage for general use,
automatically filled |
0 |
|
|
2. Water storage for general use, manually filled |
4 |
|
|
3. No water storage available |
10 |
|
|
Required Quantity of Water for Fire Extinguishment |
|
|
The required quantity in m³ is
equal to the total fire load in MJ/m² divided by 4. A smaller quantity will
can reduce the efficiency of fire fighting operations. |
|
|
0% |
4 |
|
|
70% |
3 |
|
|
80% |
2 |
|
|
90% |
1 |
|
|
100% |
0 |
|
|
Distribution network |
|
|
An adequate distribution piping
system is required, its size depending on the total water capacity required.
The distribution system shall be capable of supplying the required quantity of fire extinguishment
water to the fire scene in 2 hours without considerable pressure losses |
|
|
The following table gives the flow capacity of piping systems,
based on a maximum water velocity of 2 m/sec, which guarantees low friction
losses over larger distances. Network (looped) systems are adequate for twice
these flows. |
|
|
None or < DIA80 |
0 |
|
|
DIA 80 (3") |
34,3 |
|
|
DIA100 (4") |
59,2 |
|
|
DIA150 (6") |
134,3 |
|
|
DIA200 (8") |
232,3 |
|
|
DIA250 (10") |
366,8 |
|
|
DIA300 (12") |
526,1 |
|
|
DIA350 (14") |
676,9 |
|
| NA |
Distribution
network supply capacity |
|
|
|
|
ADEQUATE |
0 |
|
|
LIMITED |
2 |
|
|
NONE |
6 |
|
|
|
NORMAL PROTECTION FACTOR N |
|
|
Normal
protection means the chain: discovery - alarm - manual intervention |
|
|
|
Discovery and warning |
|
|
A correct normal chain of
warning consist of means of discovery, a guaranteed warning
system to the fire service and an audible signal to the occupants to evacuate
the building if required. |
|
|
“means of discovery” of a fire : e.g. continuous human presence
in the building and/or a watchman service. |
|
|
A “warning system” to signal
the existence of a fire to the fire service: this can be a telephone network
with a “fire call” number, or a manual push button system linked to the guard
post who will call the fire service, or linked to an automatic call system
for the fire service, or any other organised way to contact the fire service. |
|
|
Sometimes the warning remains
local, e.g. when the guard has no instructions or means to call the fire
service. This will be penalised. |
|
|
There must be an audible alarm
signal to the occupants to evacuate
the compartment. In noisy environments a visual signal may also be required. |
|
|
First intervention means. |
|
|
The usual means for a first
intervention are hand extinguishers, hose reels and inside hose stations. The
type and number of the equipment must be adapted to the risk. Each country
has its own rules. |
|
|
Local standards should be used
to define the number and type of hand held and mobile extinguishers. Hose
reels and hose stations should be located in such a way that any part of the
building can be reached by at least one hose jet. Hose reels are adequate for
buildings with a low fire load and untrained users Hose stations are
preferred where the fire load is high and where the people are trained. |
|
|
Portable and Mobile extinguishers |
|
|
1. Extinguishers adequate (type and
quantity) |
0 |
|
|
2. Extinguishers absent or of inadequate numbers or types |
2 |
|
|
Hose reels and/or hose stations |
|
|
1. Adequate number and location |
0 |
|
|
2. Inadequate numbers or location |
2 |
|
|
3. None |
4 |
|
|
Fire brigade arrival time |
|
|
The time between the discovery
of the fire and the first intervention of the fire brigade is the period
where the fire can develop while those in the building fight the fire. |
|
|
1. First fire brigade arrival in less
than 10 min |
0 |
|
|
2. Arrival after 10 to 15 min |
2 |
|
|
3. Arrival after 15 to 30 min |
5 |
|
|
4. More than 30 minutes delay |
10 |
|
|
Occupants' training |
|
|
The training in the use of the
manual means received by the occupants, is of great importance during that
first period. |
|
|
1. All occupants know how to use
extinguishers, hose stations |
0 |
|
|
2. Only a limited number of persons trained |
2 |
|
|
3. No extinguisher training given |
4 |
|
|
|
SPECIAL PROTECTION FACTOR S |
|
|
Under
special protection the following are considered: automatic fire detection,
improved water supplies, automatic fire protection systems, well equipped
fire brigades. |
|
|
Automatic
detection |
|
|
Automatic detection systems
speed up the discovery of a fire and the fire brigade intervention. They can
only be considered if there is a guaranteed connection to the fire brigade,
which will immediately react to the signal. |
|
|
Sprinkler systems connected to a
fire alarm by flow switches can be considered as slow thermal detection
systems. Smoke and flame detectors will be considered as fast detectors.
Electronic supervision of the system and individual identification of a small
fire zone (e.g. per detector) will give extra bonuses. |
|
|
None |
0 |
|
|
1. Automatic detection by sprinklers + flow or pressure switch |
4 |
|
|
2. by thermal (heat)
detectors |
5 |
|
|
3. by smoke or flame
detectors |
8 |
|
|
4. by smoke alarm units |
2 |
|
|
|
Improved water supplies |
|
|
The water supplies are of prime
importance for fire fighting. Rivers, lakes and any other water storage that
can guarantee 4 or more times the quantity of water needed are considered as
inexhaustible. |
|
|
The
water has to be conveyed to the fire scene by a flow/pressure source with a
reliable energy source : a water
tower, pump, elevated reservoir.. |
|
|
Single flow/pressure source |
0 |
|
|
Highly reliable : One water
storage with a double flow/pressure source[1] |
5 |
|
|
Duplicated highly reliable: two storages, each with a flow/pressure
source |
12 |
|
|
|
Automatic protection for the
compartment. |
|
|
Consider at this point only
automatic protection systems that cover the entire compartment. Partial
systems for critical items are taken into account with factor Y. |
|
|
None |
0 |
|
|
1. Sprinklers with one (public) water supply |
11 |
|
|
2. Sprinklers with one independent water supply |
14 |
|
|
3. Sprinklers with two independent water supplies |
20 |
|
|
Responding fire station |
|
|
1. Full time station
24h/24 7d/7 |
8 |
|
|
2. Professional crewed station ( day time crewed, night time
retained ) |
6 |
|
|
3.
Retained station (part time professionals) |
4 |
|
|
4. Volunteer crewed station |
2 |
|
|
|
Industrial private fire brigade |
|
|
None |
0 |
|
|
1. Part time industrial fire brigade (working hours) |
6 |
|
|
2. Full time industrial fire brigade 24h/24 7d/7 |
14 |
|
|
|
FIRE RESISTANCE FACTOR F |
|
|
The
fire resistance factor F is defined by the fire resistance of the building
elements, but with a correction for the value of the special protection S.
Such correction is necessary as the presence of active fire protection
systems reduces somewhat the benefit of passive protection. |
|
|
|
|
|
The average fire resistance is
calculated with the fire resistance in minutes of the structure, the outside
walls, the roof or ceiling, and the inner walls. |
|
|
In
most countries, the fire rating of construction elements will be expressed in
minutes as defined by tests based on the ISO R 834 time/temperature
curve. |
|
|
For
structural building elements the main criterion is stability, although other
requirements such as thermal insulation, smoke- and flame tightness and other
features are also in use for certification. |
|
|
|
|
|
FRAME considers stability only
for load bearing elements such as columns, beams, floors and roofs. |
|
|
For partitions
(subcompartmentation) flame tightness and insulation are required. |
|
|
The following limitations also apply |
|
|
1. To avoid unrealistic high values, do not use fire ratings higher than
120 minutes. |
|
|
2. Do not use higher values for outside walls, roof or ceiling and inner
walls than for the structure. |
|
|
3. For mixed construction elements, use the rating of the weakest part. |
|
|
4. Windows in outside walls can be neglected if they cover less than 5 %
of the wall area. |
|
|
5. The rating of roofs and ceilings is mainly defined by the underside. |
|
|
6. For buildings with sprinklers
designed to protect the structure or the roof, the duration of the water
supply can be taken as the fire rating, but not for more than 60 minutes. |
|
|
7. Consider only interior walls
which subdivide the compartment in fire areas, none of them should be more
than 25 % of the compartment, and no area should be larger than 1000 m² |
|
|
|
ESCAPE FACTOR U |
|
|
The escape factor U takes into
account all elements of the special protection that decrease the evacuation
time or reduce the development of the fire. Additional compartmentation and
protection of the exit paths are also evaluated. |
|
|
Automatic detection systems
speed up the discovery of a fire and the evacuation. The same values apply as
for factor S, the special protection. |
|
|
Compartmentation
and exit path protection will reduce smoke and heat spread. Shortening the
exit paths and good signage will allow the occupants to move faster into a
safe area. |
|
|
Automatic fire detection systems |
|
|
Compartment wide fire detection
systems, which are already entered for the special protection factor S are
automatically taken into account for the calculation of the escape factor U. |
|
|
Partial fire detection in
critical areas, e.g. in escape routes or increased hazard rooms can be
considered here. A small bonus is given , when less than 300 persons have to
be evacuated. |
|
|
Subcompartments |
|
|
None |
0 |
|
|
1. EI30
Subcompartments (fire areas of max.1000 m²) |
2 |
|
|
2. EI60
Subcompartments (fire areas of max.1000 m²) |
4 |
|
|
|
Type of stairways for evacuation |
|
|
No stairs used for exit |
0 |
|
|
1. Open inside stairs |
0 |
|
|
2. Single enclosed inside stair |
1 |
|
|
3. More than one enclosed inside stair |
2 |
|
|
4. At least one enclosed and smoke protected inside stair |
3 |
|
|
5. More than one enclosed and smoke protected inside stair |
4 |
|
|
6. Inside stair(s) and 1 outside stair |
6 |
|
|
7. Inside stair(s) and more than 1 outside stair |
8 |
|
|
8. Inside stair and outside toboggan or ladders for 1st / 2nd floor |
2 |
|
|
|
Horizontal exits |
|
|
No horizontal exits |
0 |
|
|
1. Horizontal exit to adjacent compartment min. 50% of required capacity |
2 |
|
|
2. Horizontal exit(s) to adjacent compartment(s) 100% of required
capacity |
8 |
|
|
|
|
Sprinkler protection |
|
|
None |
0 |
|
|
1. Sprinklers only in areas with increased fire risk |
5 |
|
|
2. Whole
compartment protected by sprinklers |
10 |
|
|
|
|
|
SALVAGE FACTOR Y |
|
|
The salvage factor Y evaluates
those physical provisions that protect sensitive parts of the activity
against the impact of a fire, and organisational measures to assure a swift
restart of the activities if necessary on an other location. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|