Schuine rand: Go to Info FRAME
Subject of this analysis:  
Building identification name of the building   PRINT REPORTS
Location    
Schuine rand: Print report
FULL
Schuine rand: Print report
Reference status
Schuine rand: Print report
Variant 1
Schuine rand: Print report
Variant 2
Schuine rand: Print INFO PAGES
Address    
City - Country    
 
Identification of the compartment and the occupancies / activities present.  
identification of the compartment  
 
Author of this calculation  
   
 
Date of this analysis date(s) of the analysis  
 
Description of the Fire safety concept of the reference status  
The reference situation is usually the actual status.  
 
Description of the Fire safety concept of Variant 1.  
Variant 1 is usually  the proposed improvements, e.g. the provision of automatic fire detection  
 
Description of the Fire safety concept of Variant 2.  
Variant 2 can be used for an alternative proposition, e.g. improving the fire resistance  
 
Risk for: Reference Variant 1 Variant 2  
 
  Property R 1,13 0,78 1,23  
 Occupants R1 0,96 0,96 1,25  
 Activities R2 0,87 0,59 0,92  
           
Potential risk P 1,73 1,73 2,25  
P1 1,35 1,35 1,76  
P2 1,28 1,28 1,35  
Schuine rand: Go to INFO P
 
Schuine rand: P- REF
Schuine rand: P- V1
Schuine rand: P-V2
 
Acceptable risk A 1,19 1,19 1,19  
A1 0,87 0,87 0,87  
A2 0,96 0,96 0,96  
Schuine rand: Go to INFO A
 
Schuine rand: A-REF
Schuine rand: A-V1
Schuine rand: A-V2
 
Protection Level D 1,28 1,86 1,53  
D1 1,61 1,61 1,61  
D2 1,52 2,25 1,52  
  Fo 1,30    
Schuine rand: Go to INFO D
Schuine rand: D-REF
Schuine rand: D-V1
Schuine rand: D-V2
 
 
 
Orientation Value Ro, Initial Risk[1] 1,12  
Proposed Fire protection concept, based on Ro  
 of  "Reference"  Add automatic fire detection  
 
Info on Ro    
 
0 Use manual fire protection  
1 Add automatic fire detection  
1,6 Install sprinklers    
2,7 Sprinklers with improved water supplies  
4,5 Too hazardous: reduce risk  
 
 
 
 
 

[1]
Use of the orientation value Ro, the Initial Risk.
To find the most efficient protection, the easiest way is to define an adequate level of protection for the property,  adding supplementary protection for the people and the activities if required.
  To facilitate the choice, one can now calculate the orientation value of Ro, the initial risk, with the values of P, A and the structural fire resistance Fo.