| name of
the building |
|
|
identification
of the compartment |
|
|
|
reference status |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Calculation
of the Protection Level D |
|
The reference
situation is usually the actual status. |
|
|
|
|
|
|
|
| DATA |
Symbol |
Unit |
|
Results |
|
|
|
Comments[1] |
|
| WATER
SUPPLY Factor [2] |
|
|
|
|
|
|
|
| Water storage type |
w1 |
|
1. Water
storage for general use, automatically filled |
0 |
|
0 |
|
|
|
|
|
|
| Water storage
capacity |
|
m³ |
Estimated
capacity of water storage available for fire fighting |
158 |
m³ |
|
|
|
|
|
|
|
|
|
| |
|
m³ |
Required
Capacity for fire extinguishment[3] |
175 |
m³ |
|
|
|
|
|
|
|
|
|
| |
w2 |
|
Available
capacity as % of required |
90% |
1 |
1[4] |
|
|
|
|
|
|
|
|
| Distribution network |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Nominal
diameter of main water piping |
|
mm |
DIA
80 (3") |
flow capacity |
34,3 |
|
|
|
|
|
|
|
|
|
| Looped
network ? |
|
|
yes |
total m³/h |
68,6 |
|
|
|
|
|
|
|
| |
w3 |
|
Distribution
network supply capacity |
LIMITED |
|
2 |
|
|
|
|
|
|
|
| Hydrant hose
connections[5] |
|
m |
Building perimeter ( = 2 *
(b+l)) |
180 |
m |
|
|
|
|
|
|
| |
|
# |
Number
of available 2.5" (70) connections[6] |
4 |
|
|
|
|
|
|
| |
|
# |
Number
of available 3" (80) connections[7] |
0 |
|
|
|
|
|
| |
|
# |
Number
of available 4" (110) connections[8] |
0 |
|
|
|
|
| |
|
|
Equivalent
number of 2.5" (70) connections[9] |
4 |
|
|
|
| |
w4 |
|
Average
distance between connection on the building perimeter |
45,00 |
|
0 |
|
| Static
pressure[10] |
|
m |
Floor
level height H+ or H- + ceiling height |
4 |
|
|
|
| |
|
|
Required
network static pressure |
3,9 |
bar |
|
|
| |
w5 |
bar |
Available
static pressure in the distribution network |
5 |
bar |
0 |
|
|
|
| |
|
|
w |
= |
3 |
|
|
|
|
|
|
|
| |
|
|
WATER SUPPLY
Factor |
W |
= |
0,86 |
|
| Normal protection Factor [11] |
|
|
|
| Discovery |
n1 |
|
Continuous
human presence , watchman service |
yes |
|
0 |
|
|
| warning |
|
|
There is also a
(manually operated) warning system |
yes |
|
0 |
|
|
| Call to fire
brigade |
|
|
Guaranteed transmission
to the fire service |
yes |
|
0 |
|
|
| Occupants
alarm |
|
|
There is also an alarm to
the occupants |
yes |
|
0 |
|
|
| Extinguishers |
n2 |
|
1.
Extinguishers adequate (type and quantity) |
0 |
|
0 |
|
|
| Fire hose
stations[12] |
n3 |
|
1.
Adequate number and location |
0 |
|
0 |
|
|
| Fire brigade
arrival |
n4 |
|
2.
Arrival after 10 to 15 min |
2 |
|
2 |
|
|
| Occupants'
training |
n5 |
|
2. Only a limited
number of persons trained |
2 |
|
2 |
|
|
| |
|
n |
= |
4 |
|
|
|
|
|
| |
|
|
Normal
protection Factor |
N |
= |
0,81 |
|
|
|
|
|
|
|
| Special protection factor |
|
|
|
|
| Automatic
fire detection |
s1 |
|
Guaranteed
transmission of the detection signal to the fire brigade directly / through control room[13] |
yes |
|
|
|
|
|
|
| |
|
|
None |
0 |
|
0 |
|
|
|
|
| |
|
|
Electronic supervised
system - fault monitoring |
no |
|
0 |
|
|
|
|
|
| |
|
|
Individual
identification of small fire zones (detector, room) |
no |
|
0 |
|
|
|
|
|
| Improved water supply |
s2 |
|
Inexhaustible water
supplies (4 times adequate)[14] |
no |
|
0 |
|
|
|
|
|
| |
s3 |
|
Reserved for fire
fighting only |
no |
|
0 |
|
|
|
|
|
| Control of water supply |
s4 |
|
Under control of
building user (independent) |
no |
|
0 |
|
|
|
|
|
| Pressure / Flow energy source |
s5 |
|
Single flow/pressure source[15] |
0 |
|
0 |
|
|
|
|
|
| Sprinkler protection |
s6 |
|
None |
0 |
|
0 |
|
|
|
|
|
| Other automatic |
s7 |
|
Other automatic
extinguishing systems (CO2, foam, inert gas) |
no |
|
0 |
|
|
|
|
|
| Responding fire station |
s8 |
|
1. Full time station
24h/24 7d/7 |
8 |
|
8 |
|
|
|
|
| Industrial fire brigade |
s9 |
|
None |
0 |
|
0 |
|
|
|
|
| |
|
|
|
s |
= |
8 |
|
|
|
| |
|
|
Special
protection factor |
S |
= |
1,48 |
|
| Fire resistance factor |
|
|
| Structural /compartments |
fs |
min. |
Average fire
resistance (REI) of the structural and separating elements: |
30 |
min. |
30 |
|
|
| Outside
walls |
ff |
min. |
Average
fire resistance of the outside walls ( E = flame tightness) |
30 |
min. |
30 |
|
|
| Ceiling or
roof |
fd |
min. |
Average
fire resistance of the ceiling or the roof (RE) |
30 |
min. |
30 |
|
|
| Interior
walls[16] |
fw |
min. |
Average
fire resistance of interior walls (EI) |
0 |
min. |
0 |
|
|
| |
|
|
Calculated
weighed average for fire resistance |
f |
= |
26,25 |
|
| |
|
|
Initial
structural fire resistance (stability) |
Fo |
= |
1,30 |
|
| |
|
|
Fire resistance
factor [17] |
F |
= |
1,24 |
|
| Escape protection factor |
|
|
| Automatic fire detection |
u1 |
|
Some data are already entered at
factor S |
|
|
|
|
| |
|
|
None |
0 |
see
at S |
0 |
|
| |
|
|
Electronic supervised
system - fault monitoring |
no |
see
at S |
0 |
|
| |
|
|
Individual
identification of small fire zones (detector, room) |
no |
see
at S |
0 |
|
| |
|
|
Partial detection
system, only in areas critical for people safety[18] |
no |
|
0 |
|
|
| |
|
|
No more than 300
persons to be warned simultaneously |
yes |
|
2 |
|
|
| |
|
|
Evacuation alarm with
spoken messages by voice communication system |
no |
|
0 |
|
|
| Subcompartments |
u2 |
|
None |
0 |
|
0 |
|
|
| Exit path protection |
u3 |
|
1. Open inside stairs |
0 |
|
0 |
|
|
| Horizontal exits |
|
|
No horizontal exits |
0 |
|
0 |
|
|
| Signage and illumination |
|
|
Exit paths completely
marked and illuminated |
yes |
|
4 |
|
|
| Sprinklers? |
u4 |
|
None |
0 |
|
0 |
|
|
| Other automatic system |
u5 |
|
Other
automatic extinguishing systems (CO2, foam, inert gas) |
no |
see
at S |
0 |
|
| Smoke vents actuation |
u6 |
|
Smoke venting
actuated by automatic detection |
no |
|
0 |
|
|
| Responding fire station |
u7 |
|
1. Full
time station 24h/24 7d/7 |
8 |
see
at S |
8 |
|
| Industrial fire brigade |
u8 |
|
None |
0 |
see
at S |
0 |
|
| |
|
|
|
u |
= |
14 |
|
| |
|
|
Escape
protection factor |
U |
= |
1,98 |
|
| Salvage
factor |
|
|
|
|
|
|
| Compartmentation |
yi |
|
None |
0 |
|
0 |
|
| PHYSICAL
PROTECTION |
|
|
|
|
|
|
|
| Detection |
yi |
|
Partial detection
system, only in areas critical for business continuity[19] |
no |
|
0 |
|
|
| Sprinkler |
|
|
Local sprinkler
protection for critical equipment[20] |
no |
|
0 |
|
|
| Other systems |
yi |
|
Other LOCAL automatic
extinguishing systems (CO2, foam, inert gas) |
no |
|
0 |
|
|
| ORGANISATION |
|
|
|
|
|
|
|
| FINANCIAL |
yi |
|
Safeguarded
financial and economical data[21] |
yes |
|
2 |
|
|
| EQUIPMENT |
yi |
|
Easy
access to spare parts and replacements |
yes |
|
4 |
|
|
| REPAIRS |
yi |
|
Repairs possible with
minimal help |
yes |
|
2 |
|
|
| RELOCATION |
|
|
Immediate transfer of
activities possible |
no |
|
0 |
|
|
| COOPERATION |
yi |
|
Written agreements
for relocation exist |
no |
|
0 |
|
|
| PRODUCTION
CENTRES |
yi |
|
Production
capacity available at more than one location |
no |
|
0 |
|
|
| |
|
|
y |
= |
8 |
|
| |
|
|
Salvage factor |
Y |
= |
1,48 |
|
| Protection levels D |
|
|
| |
|
|
Protection levels for: |
|
|
|
|
|
| WATER SUPPLY Factor |
W |
0,86 |
Property |
D |
1,28 |
|
|
|
| Normal protection Factor |
N |
0,81 |
Occupants |
D1 |
1,61 |
|
Date of this analysis |
|
| Special protection
factor |
S |
1,48 |
Activities |
D2 |
1,52 |
|
|
|
| Fire resistance factor |
F |
1,24 |
|
|
|
date(s) of the analysis |
|
| Escape protection factor |
U |
1,98 |
|
|
|
|
|
| Salvage factor |
Y |
1,48 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|