$15 million Sight and Sound Theater Fire, Lancaster County Pennsylvania.This report refers to a fire described in a report of the United States Fire Administration. This report can be found at http://www.usfa.fema.gov/techreps/ From this report , the following overview was copied, because it gives the main key issues that resulted in the catastrophic fire. A FRAME calculation was made to check the validity of the method and the consistency of FRAME with expert knowledge. To show the consistency of FRAME with the expert remarks, a column with references to the calculation is given in the table. The FRAME generated report is shown further on. OverviewOn the morning of January 28, 1997, in the Lancaster County , Pennsyl1vania township of Strasburg, a fire caused the collapse of the state-of-the-art, seven year old Sight and Sound Theater and resulted in structural damage to most of the connecting buildings. The theater was a total loss, valued at over $15 million. The stage area was undergoing renovation and the theater was closed to the public, however, approximately 200 people, construction staff and employees were in the building at the time the fire started. Although the theater was built to conform to a two hour, fire rated assembly code requirement, many other fire protection features that could have assisted in saving the structure and reducing the damage were not present. Further contributing to the resultant loss, was the failure of the alarm system to notify the fire dispatch communications center and the lack of an adequate, readily available water supply. The volunteer fire departments that responded were faced with difficult fire conditions and tactical challenges for which they had not been adequately trained, and were without the benefit of adequate pre-planning. Local fire service suggestions for built-in fire suppression and smoke ventilation systems during the pre-construction plan review phase were ignored. While the incident was influenced by many conditions and situations which contributed to the large fire loss, fortunately there was no loss of life and only six minor injuries to the construction company staff. If the 1,400 seat capacity auditorium had been full, the situation could have been catastrophic. The lessons learned as a result of this fire and collapse are similar to observations from comparable incidents in recent history. The Wolftrap Farm Theater and Pavilion fire in Fairfax County Virginia in 1988 suffered a total loss in the stage, props, dressing rooms and storage area. The pre-construction recommendation for a fire sprinkler system had not been heeded. When the facility was rebuilt, it was totally sprinkled. The McCormick Place exhibition hall fire in Chicago, Illinois in 1967 was a public assembly occupancy built with fire protected steel construction and no sprinkler system. Fortunately the fire started in the early morning hours; the possibility of life loss would have been staggering had the fire occurred during the day. This fast burning, high rate of heat production fire caused complete collapse of the building. The fire was discovered early but the alarm was delayed while maintenance personnel tried to control the fire. The new (rebuilt) McCormick place has a hydraulically calculated sprink1er system, smoke venting system in addition to one hour rated fire resistance protection on structural steel. The lessons learned here are not new. These examples are similar in situation and outcome to the Sight and Sound theater fire.
FRAME ApproachAccording to FRAME the following improvements would be required:
The FRAME generated report for the esisting situation is given below: F.R.A.M.E. calculation report The calculculation is made for: Sight_and_Sound_Theater location: Strasburg_Pennsylvania The compartiment is: main The occupancy or use is:: theater Date of the calculation: 1997.08.01 Version: US_fire_administration CALCULATION of the POTENTIAL RISKS Data of the compartment : The fire load 'immobile' Qi is (in MJ/m²) : 100.00 The fire load ' mobile' Qm is (in MJ/m²) : 1500.00 This gives for the fire load factor q : 1.59 The temperature ris T in °C is: 200.00 The average dimension m (in meters) is: 0.30 The combustibility class, M is: 3.00 This gives for fire spread factor i: 1.15 The theoretical length l is: 60.96 meter The equivalent width b is: 60.96 meter This gives for the area factor g: 1.83 The level number E is: 0.00 This gives for the level factor e: 1.00 The ceiling heigth h is: 12.19 meter The flow of the ventilation system is (in Nm³/h): 0.00 The aerodynamic surface of the smoke vents is (in m²): 0.00 m² The surface of the windows in the roof and upper third of the walls is: 0.00 m² The smoke venting ratio is: 0.00 This gives for the venting factor v: 1.16 The heigth difference with the access level is: 0.00 meter The number of access directions is: 3.00 This gives for access factor z: 1.05 These data give the following results: The potential risk P for property is: 4.06 The potential risk P1 for the persons is: 2.22 The potential risk P2 for the activities is: 2.56 CALCULATION of the ACCEPTANCE LEVELS The following elements determine the possibility of starting a fire: Main activity: Non industrial activities Heating systems: Heat transfer through water, steam, or solids ; Heat generator in a fire separated room Energy source: electricity, coal, fuel oil Electrical installations: In compliance with the rules and regularly checked Explosion hazards: No explosion hazard Secondary activities : Secondary welding operations This gives for the activation factor a : 0.10 The following elements interfere with the evacuation of the compartment: The number of persons to evacuate is: 1500.00 The number of exit units is: 29.00 The number of exit paths is: 2.00 The mobility factor p is defined as follows: mobile but dependent persons, there is a danger for panic This gives for evacuation time factor t: 0.36 The following elements define the value of the content: Replacement factor c1 is: 0.00 The value of the content is estimated at:15.00 Million US$ with an inflation correction for 2000 of : 1.00 This gives for content factor c: 0.04 The environment factor r is defined with Qi and M and is: 0.50 The dependency factor d is: 0.30 These data give the following results: The acceptance level A for the property is: 1.10 The acceptance level A1 for the persons is: 0.64 The acceptance level A2 for the activities is: 1.16 THE ORIENTATION VALUE Ro, The Initial Risk : The fire resistance of the structure is: 120.00 This gives with the calculated values of P and A, an orientation value Ro of: 1.80 CALCULATION of the PROTECTION LEVELS The following elements define the value of the water supplies: Type of storage: Water storage for general use, automatically filled; The available quantity is adequate Distribution network: none This gives for factor W: 0.54 The following elements define the value of the normal protection : Notification: All the elements of the notification chain are present Manual extinguishment means: Extinguishers adequate, Hose stations adequate Arrival time for the fire brigade: Arrival after 10 to 15 min. Training of people: Only a limited number of persons trained This gives for factor N: 0.81 The following elements define the value of the special protection : Type of automatic detection: Automatic detection by thermal (heat) detectors , with electronic supervision of the system type of fire brigade: Small permanent team + volunteer public fire brigade This gives for factor S: 1.80 This factor S and the following elements define the value of the fire resistance : The fire resistance of the structure is: 120.00 The fire resistance of the exterior walls is: 60.00 The fire resistance of the ceiling or roof is: 60.00 The fire resistance of the internal walls is: 0.00 This gives for factor F : 1.73 The following elements define the value of the escape possibilities: Detection and signalisation: Automatic detection by thermal (heat) detectors , with electronic supervision of the system Savegarding of exit paths: Complete evacuation plan with adequate signalling Protection by: Small permanent team + volunteer public fire brigade This gives for factor U : 2.08 The following elements define the value of the salvage factor : Protection and organisation: epairs possible with minimal help This gives for factor Y : 1.00 These data give the following results: The protection level D for the property is: 1.37 The protection level D1 for the persons is: 1.69 The protection level D2 for the activities is: 0.79 The calculated risk R is for the property: 2.70 The calculated risk R1 is for the persons: 2.04 The calculated risk R2 is for the activities: 2.79 These values are far away from the R= 1 goal set by FRAME. The conclusion drawn by using FRAME can only be that the building was poorly protected for property , people and business.
|
||